Bedding
construction is very crucial in the installation of clay pipes being
rigid. To determine the adequacy of the
type of bedding construction used on the site, SVCP offers free technical
advice/assistance on the Static Load Calculations of clay pipes. Static Load Calculation determines the
external or design load on the pipes used which are influenced by the trench
width pipes are laid, depth of backfill cover and the type of bedding in which
the pipes are laid.
Under
the principle that the maximum total external load on the pipes, we must not
exceed the minimum value of the pipe strength, FN multiplied by the appropriate
value of the bedding factor, BF and divided by a suitable design factor of
safety, FS generally taken as 1.25.
i.e Wc £ FN x BF
1.25
Computation
of the trench load is done using Marston’s formula
¾2
Narrow
Trench load, Wc = 1-e-2Km’
H/Bd
g Bd
2 Km’
Where Km’ = the product of active earth pressure coefficient &
coefficient of sliding
friction within a mass of fill
H = depth
of cover
Bd = trench width
g = unit
weight of backfill material
¾2
and Wide Trench load, Wc’ = [1.50 H/Bc-0.07]
g
Bc when
rsdp
is taken as 0.5
¾2
or, Wc’ = [1.59 H/Bc-0.09]
g
Bc when rsdp
is taken as 0.7
where Bc = outer diameter of pipe
rsd = settlement ratio
p = projection
ratio
Total design or
external load = lesser of the narrow or wide trench load +
surcharge + water load
Bedding Factor can therefore be
computed once the total external load has been determined. The value of the bedding factor for a
particular method of construction is not a precise figure but is affected by
the quality of workmanship. It is determined
by the effectiveness with which bedding materials and backfill around the pipe
distribute the loads and support pressures acting on it. As design cannot be separated from
construction, calculation of the bedding factor assumes a reasonable standard
of workmanship and supervision on site.
As
a guide, reference is made to the recommended types of bedding construction by
the Clay Pipe Development Association Limited with the corresponding Bedding
Factor.
References:
1. Transport Research Laboratory – “Simplified
Tables of External Loads on Buried Pipelines” and “Guide to Design Loadings for
Buried Rigid Pipes”
2. Clay Pipe Development Associated Limited –
“Design Tables for Determining the Bedding Construction of Vitrified Clay
Pipelines”